Chapter 5, Section 3
Part of AM Radio Facts and Trivia: The AM Broadcast Band in the USA. Updated November 15, 2026.
An AM transmitter site uses more copper than almost any other small building in the country. Some of it is famous: the buried radial field that the antenna works against (see Ground Radial Systems), often 120 wires a quarter-wavelength long fanning out from each tower, adding up to tens of miles of copper in the dirt. But there's a second, less-visible copper system inside and around the transmitter building itself, and it's doing three different jobs at once.
Three grounds, one reference. What looks like a single "ground" is really three:
| Job | What it does |
|---|---|
| RF bonding | Ties every piece of equipment, rack, and cabinet to one common potential so the building doesn't become part of the antenna, and so stray RF doesn't get into the audio and control gear |
| Lightning | Carries a tower strike, potentially 20,000 amps from a million volts, safely to earth around the equipment instead of through it |
| AC safety | The ordinary code-required fault ground that keeps the chassis of everything at earth potential so a fault can't electrocute someone |
Table 5.3-1
The cardinal rule is that all three must be bonded together to a single-point (reference) ground, a star, not a daisy-chain, so there's never a dangerous voltage difference between two grounded things during a strike.
Strap, not wire. Walk the building and you'll see wide, flat copper strap (three or four inches across) rather than round wire. The reason is impedance: at RF, and against the microsecond rise-time of a lightning surge, a flat strap has far lower inductance than a round conductor of the same copper. A main strap runs from the radial-field junction at the tower base into the building, bonds to the AC ground, continues to a designated point inside the transmitter cabinet, and then branches out to every rack and every box. Skip that bonding at a real AM station and, as the old hands put it, you turn every semiconductor junction in the building into a tiny crystal radio: the station's own signal rectifying into the audio chain.
Built to send lightning the other way. The art of a good AM ground is steering the strike. The transmitter and electronics sit on a "stub" off the reference ground, so lightning arriving down the tower finds its easy path to earth at the reference point and never bothers to detour through the gear. A ground ring with driven rods often circles the building, tied to the reference ground at exactly one point. Every coax and control line enters through a single copper entrance panel (the "ground window"), where surge protectors bolt directly to the strap before anything crosses the wall, and a classic trick is to coil five or six turns of the incoming line right there, because lightning travels in a straight line and won't follow the curve. Connections are exothermically welded (Cadweld) or clamped with anti-corrosion compound, and bends are kept gentle: a sharp 90° bend adds just enough inductance to spoil the whole scheme.
Drawing 5.3-2
The copper-theft problem. All that exposed copper has made AM sites a target. Thieves strip ground straps and radial wire for scrap, which is both dangerous (it can leave equipment ungrounded and detune the array) and expensive to repair, a modern cousin of the outright tower theft that took down WJLX 1240.
The trivia. The signal an AM station radiates is only as good as the copper it can't transmit through. The radial field is the invisible other half of the antenna; the building strap is the invisible thing keeping the building out of the antenna and the lightning out of the racks. It's the least glamorous part of the plant: buried wire and flat bar bolted to a wall, and pulling any of it out degrades the signal, invites interference, and removes the path that keeps a strike from finding the Jesus stick's job the hard way.
Sources: Radio World ("Field Service Tips: Grounding," Mark Persons) · Mike Holt Enterprises electrical forums (AM tower strap/bonding practice) · ICO Optics (grounding and lightning protection for radio installations) · Nautel grounding guidance.
© 2026 Chris, N6JET. Free to read and share for non-commercial use with credit (Creative Commons BY-NC 4.0). Not for sale.
All AM radio stories by subject · AM radio interactive tools and simulators · AM Trivia Challenge quiz